Which mini splits put out the most heat at 5°F, and which keep the most of their 47°F output?

Updated November 22, 2026

On heat output at 5°F, a large unit leads: the Senville SENA-55HF-MOA, an outdoor unit listed without an indoor unit, is certified for 48,000 BTU/h at 5°F, the most of any pairing from the four brands, which is 87% of its output at 47°F. On the share of 47°F output kept at 5°F, smaller units lead: the Senville SENE-09EL-OH, SENE-12EL-OH and SENE-18EL-OH, each with its SENE indoor unit, put out 113% of their 47°F output at 5°F. ENERGY STAR's cold climate criteria require at least 70%.

Pairings listed as ENERGY STAR cold climate. 20 pairings with heat output at 5°F 30,000 or higher, sorted by heat output at 5°F, highest first.

Outdoor unitBrandSeriesIndoor unitCooling BTU/hHeat at 47°F BTU/hHeat at 5°F BTU/hKept at 5°F % of 47°FCOP at 5°FRefrigerantSeller
SENA-55HF-MOASenvilleSENAnot listed53,00055,00048,00087%2.10R-454BSenville
SENA-48HF-MOASenvilleSENAnot listed47,00049,00047,00096%2.00R-454BSenville
DIY-MULTI6-55HP230D-OMRCOOLDIYnot listed47,00055,00046,00084%2.00R-454BMRCOOL
SENA-48HF-MOBSenvilleSENAnot listed48,00049,00045,00092%2.00R-410ASenville
048-TLP-MODU-1D6DellaTLPnot listed55,00055,00042,00076%2.00R-454BDella
048-TPH-MODU-1D6DellaTPHnot listed48,00048,00041,00085%1.75R-454BDella
YN060GLSI24M6GPioneerQuantum Ultra Multinot listed55,00055,00041,00075%1.75R-454BPioneer
YN048GMSI20RUGPioneerYNCB048GMSILDFHG48,00050,00040,50081%2.11R-454BPioneer
YN048GMSI20RUGPioneerYNUB048GMSILDFHG48,00050,00038,50077%1.95R-454BPioneer
YN048GMSI20RUGPioneerYNRB048GMSILDFHG48,00050,00038,00076%2.00R-454BPioneer
DIY-MULTI6-48HP230D-OMRCOOLDIYnot listed43,00048,00037,00077%2.00R-454BMRCOOL
SENA-36HF-MOBSenvilleSENAnot listed36,00036,00037,000103%2.00R-410ASenville
MULTI6-48HP230C-OMRCOOLMULTInot listed47,00048,00036,00075%2.00R-454BMRCOOL
SENA-36HF-MOASenvilleSENAnot listed36,00036,00036,000100%2.00R-454BSenville
YN048GMFI18RUEPioneerYNUB048GMFILCFHD48,00050,00035,00070%1.85R-410APioneer
SENA-33HF-OGSenvilleSENASENA-33HF-IGG33,00036,00035,00097%1.98R-454BSenville
SENA-33HF-OQSenvilleSENSENA-33HF-IQ33,00035,00034,60099%1.80R-410ASenville
048-TLP-MODU-1D5DellaMODUnot listed41,00042,00033,00079%1.90R-454BDella
048-TPH-MODU-1D5DellaTPHnot listed36,00036,00033,00092%1.90R-454BDella
YN050GLSI24M5GPioneerQuantum Ultra Multinot listed42,00042,00030,00071%2.00R-454BPioneer

Kept at 5°F is calculated by DIY Splits, not certified: the heat output at 5°F divided by the heat output at 47°F, both from the certified data.

The table lists the cold climate pairings with the most heat at 5°F. The SENE pairings that lead on share kept put out less heat than the table’s cut and are not in it; the heating output by temperature tool shows the share kept by every pairing.

Two different measures

Heat output at 5°F is how much heat a pairing delivers at that temperature. The share kept is that output divided by the pairing’s output at 47°F. A large unit can lead the first and still lose more of its heat; a small unit can lead the second and still deliver less. The SENE-09EL-OH with SENE-09EL-IHH is certified for 13,500 BTU/h at 5°F and 12,000 BTU/h at 47°F, so its share is 113%.

Among the pairings in the table, the Senville SENA-36HF-MOB keeps the largest share: 37,000 BTU/h at 5°F, 103% of its 47°F output.

Most heat at 5°F in each size up to 24,000 BTU

Across all pairings from the four brands in each size up to 24,000 BTU:

What the cold climate listing requires

ENERGY STAR lists a heat pump as cold climate when its COP at 5°F is at least 1.75, its heating capacity at 5°F is at least 70% of its capacity at 47°F, its SEER2 is at least 15.2 and, for a non-ducted split system, its HSPF2 is at least 8.5. Its performance must also be confirmed by a controls verification procedure. COP is the heating rate divided by the electrical power used, so it measures efficiency at 5°F, not output.

A pairing that is not listed as cold climate still has certified 5°F figures. The MRCOOL DIY-12-HP-C-115C25 with DIY-12-HP-WMAH-115C25 keeps 53% of its 47°F output at 5°F.

Between the certified points

The data has certified heating figures at 5, 17 and 47°F, and none below 5°F. The same tool estimates each pairing’s output at temperatures in between.

Sources

  1. ENERGY STAR's cold climate criteria for a heat pump are a COP at 5°F of at least 1.75, heating capacity at 5°F of at least 70% of the capacity at 47°F, SEER2 of at least 15.2 and, for non-ducted split systems, HSPF2 of at least 8.5, with performance confirmed by a controls verification procedure. www.energystar.gov
  2. ENERGY STAR defines COP as the heating rate divided by the electrical power used, with no units. www.energystar.gov

Related

Data: ENERGY STAR certified heat pumps, last checked November 23, 2026