What does the EPA rule say about R-410A, R-454B and R-32 mini splits?

Updated November 22, 2026

The EPA sets a global warming potential limit of 700 for residential and light-commercial air conditioning and heat pump systems, and names mini splits as an example. The installation compliance date is January 1, 2025, and there is no installation compliance date for systems whose specified components were all manufactured or imported before then. On the EPA's 100-year figures, R-410A is rated 2,088, above the limit, while R-454B is rated 465 and R-32 675, both below it.

12,000 BTU pairings from the MRCOOL DIY, Della TP and Pioneer Diamante Ultra series, which list both R-410A and R-454B, and from the Della M and Q, MRCOOL TruInverter and Pioneer Diamante Fresh series, which use R-32. 25 pairings, sorted by Refrigerant, A to Z.

Outdoor unitBrandSeriesIndoor unitRefrigerantSEER2HSPF2Heat at 5°F BTU/hKept at 5°F % of 47°FSeller
048-MS-12K1VR-22S-M-OUTDellaM048-MS-12K1VR-22S-M-INR-3222.09.59,20075%Della
048-MS-12K2VR-21S-OUTDellaQ048-MS-12K2VR-21S-QC-INR-3221.010.08,20067%Della
048-MS-12K2VR-22S-M-OUTDellaM048-MS-12K2VR-22S-M-INR-3222.09.59,10074%Della
AEPL**MHV23S1231B1AMRCOOLTruInverterAEPL**AWM23E1231B1AR-3224.010.010,00083%MRCOOL
AEPL**MHV23S1232B1AMRCOOLTruInverterAEPL**AWM23E1232B1AR-3224.010.010,00083%MRCOOL
YN012GLUI25RPQPioneerDiamante FreshWT012GLUI25FVQR-3224.09.510,10077%Pioneer
048-TP-12K1V-22S-OUTDellaTP048-TP-12K1V-22S-INR-410A22.09.08,70073%Della
048-TP-12K2V-23S-OUTDellaTP048-TP-12K2V-23S-INR-410A23.09.59,10076%Della
DIY-12-HP-C-115C25MRCOOLDIYDIY-12-HP-WMAH-115C25R-410A22.59.06,40053%MRCOOL
DIY-12-HP-C-115CMRCOOLDIYDIY-12-HP-WMAH-115C25R-410A22.59.06,40053%MRCOOL
YN012ALFI22RPDPioneerDiamante UltraWT012ALFI22HLDR-410A22.09.08,70073%Pioneer
YN012GLFI22RPDPioneerDiamante UltraWT012GLFI22HLDR-410A23.09.59,10076%Pioneer
048-C-TP-12K1V-23S-OUTDellaTP048-C-TP-12K1V-C-INR-454B23.010.08,90072%Della
048-C-TP-12K2V-24S-OUTDellaTP048-C-TP-12K2V-C-INR-454B24.010.09,10072%Della
048-TP-12K1V-23S-OUTDellaTP048-TP-12K1V-23S-INR-454B23.010.08,90072%Della
048-TP-12K1V-23S-OUTDellaTP048-TP-12K1V-C-INR-454B23.010.08,90072%Della
048-TP-12K2V-24S-OUTDellaTP048-TP-12K2V-24S-INR-454B24.010.09,10072%Della
048-TP-12K2V-24S-OUTDellaTP048-TP-12K2V-C-INR-454B24.010.09,10072%Della
DIY-12-HP-C-115D25-OMRCOOLDIYDIY-12-HP-WMAH-115D25-OR-454B23.510.28,40070%MRCOOL
DIYHH-12-HP-C-230D25-OMRCOOLDIYDIY-12-HP-WMAH-230D25-OR-454B23.510.011,00092%MRCOOL
DIYHH-12-HP-C-230D25-OMRCOOLDIYDIYCASSETTE12HP-230D25-OR-454B22.210.811,50092%MRCOOL
YN012ALSI24RPGPioneerDiamante UltraWT012ALSI24HLGR-454B23.010.08,90072%Pioneer
YN012GLSI24RPGPioneerDiamante Ultranot listedR-454B19.08.48,80073%Pioneer
YN012GLSI24RPGPioneerDiamante UltraCT012GLSILCFHGR-454B21.010.09,00075%Pioneer
YN012GLSI24RPGPioneerDiamante UltraWT012GLSI24HLGR-454B24.010.09,10072%Pioneer

Kept at 5°F is calculated by DIY Splits, not certified: the heat output at 5°F divided by the heat output at 47°F, both from the certified data.

The ENERGY STAR data lists pairings with all three refrigerants. The finder lists every pairing and filters them by refrigerant.

What else the EPA says

The EPA’s table states the limit as a global warming potential and does not name R-410A. For systems already installed, the EPA says components for repairing existing systems are not subject to the restrictions, and that existing systems can keep being repaired.

One size, three refrigerants

The table is a sample at one size, 12,000 BTU, chosen to show the three refrigerants side by side.

In each of the MRCOOL DIY, Della TP and Pioneer Diamante Ultra series, the R-454B pairing named here rates higher on SEER2 and HSPF2 than the R-410A pairing:

These pairs are examples, and not every R-454B pairing in the table rates higher: the MRCOOL DIYHH-12-HP-C-230D25-O with DIYCASSETTE12HP-230D25-O (R-454B) is rated SEER2 22.2, below the 22.5 of the R-410A DIY pairing above. The model numbers in each pair also differ in more than the refrigerant, and the data does not say what else changed, so the table cannot show the effect of the refrigerant alone.

Among the R-32 pairings in the table, the Pioneer YN012GLUI25RPQ with WT012GLUI25FVQ and the MRCOOL TruInverter pairings are rated SEER2 24.0, and the Della 048-MS-12K1VR-22S-M-OUT with 048-MS-12K1VR-22S-M-IN 22.0.

Sources

  1. The EPA sets a global warming potential limit of 700 for residential and light commercial air conditioning and heat pump systems, names mini splits as an example, and gives an installation compliance date of January 1, 2025. www.epa.gov
  2. The same EPA table, on a page dated August 28, 2026, gives no installation compliance date for systems where all specified components were manufactured or imported before January 1, 2025, and does not name R-410A. www.epa.gov
  3. EPA 100-year global warming potentials: R-410A 2,088, R-454B 465, R-32 675. www.epa.gov
  4. The EPA says components for repairing existing systems are not subject to the restrictions, and existing systems can keep being repaired. www.epa.gov

Related

Data: ENERGY STAR certified heat pumps, last checked November 23, 2026